PG 6-401, Capacitor Tester, 6kV

The High-Voltage Pulse Generator Type PG 6-401 is designed for dielectric testing of X- and Y-capacitors with standard impulse voltages 1.6/47 µs up to 6 kV acc. to IEC 384-14, etc. The generator has the same principle of operation as the IPG 809 but allows testing capacitance values of 33 nF - 470 nF. Picture: incl. Option PA 503

PARTNER:

MARKETS:

TEST STANDARDS:

Data Sheet

SPECIFICATIONS

High-Voltage Pulse Generator PG  6 - 401

 

 

Surge testing of

 

 

  • X- and Y- capacitors 33 nF - 470 nF
  • 0.2 - 6 kV
  • 1.6 / 47 µs
  • IEC 60384-14, EN 132400
  • VDE 0565

 

 

The High-Voltage Pulse Generator Type PG 6-401 is designed for dielectric testing of X- and Y-capacitors with standard impulse voltages 1.6/47 µs up to 6 kV acc. to IEC 384-14, etc.  The generator has the same principle of operation as the IPG 809 but allows the testing capacitance values of 33 nF - 470 nF.

 

The impulse voltage output connectors are located at the top of the equipment and are protected by a dielectric cover with safety interlock. Upon lifting of the cover, switching-off of the generator or mains blackout a built-in high-voltage grounding switch discharges the test object and the internal energy storage capacitor.

Test devices are connected to a plug-in test adapter.

 

The pulse generator PG 6-401 features a microprocessor-controlled user interface and display unit for ease of use. The microprocessor allows the user to operate the generator manually or to generate, save and execute a ´user-defined´ test sequence. The test parameters, charging voltage, polarity number of pulses, pulse repetition time which are shown on the built-in display, are easily adjusted by means of the rotary encoder.

 

A standard parallel interface provides the ability to print a summary of the test parameters whilst testing is being carried out.

 

Moreover all generator functions may be computer-controlled via the isolated optical interface.

 

The generator excels by a compact design, simple handling and precise reproducibility of test pulses.

 

The generator uses maintenance-free semiconductor switches for surge current generation.

 

 

Technical specifications

PG 6-401

 

 

Mainframe

 

Microprocessor controlled LCD module

8*40 characters

Parallel printer interface for on-line documentation

25-way ´D´connector

Optical-interface for remote control of the generator

Built-in

External Trigger input

10 V an 1 kW

External Trigger output

10 V an 1 kW

Mains power

230 V / 50 /60Hz

Dimensions, 19" desktop case

453*320*520 mm3

Weight

25kg

 

 

Pulse forming network for surge testing of capacitors

33 - 470 nF

Surge voltage output amplitude, adjustable via charging voltage

0.2 - 6.0 kV ± 5 %

Waveform of impulse output voltage:

 

Rise time

1.6 µs - 0/+50%

Release time

47 µs - 0/+50%

Polarity selectable

pos/neg

Max. energy content

400 Joule

Charging time at max. charging voltage

ca. 14 sec

Internal load capacitor

3300 pF ± 10%

Damping resistor Rs

selectable

Load capacitance Cx = 33 nF

25 W

Load capacitance Cx = 47 nF

13 W

Load capacitance Cx = 68 nF

9 W

Load capacitance Cx = 100 nF

7 W

Load capacitance Cx = 150 nF

5 W

Load capacitance Cx > 180 nF

3 W

Impulse voltage divider, monitor output, BNC

ü=1000:1 ±2 %

Impulse voltage output connector

6 mm Ø

 

 

Safety test cover

 

Mounted on the top of the equipment,

Safety interlock loop connected to the limit switch

 

Dimensions, W * H * D

400 * 150 * 250 mm³

 

 

Accessories

 

Power cable, turn-key and instruction manual

 

 

 

Option PC software

 

PC Software for remote control of the generator, running under XP- WIN7, PC Interface USB/RS232, optically isolated and a light guide, 5m

 

 

 

Option Connection PA 503

 

Connection of IPG 809 at the safety test cover PA 503, provided Safety interlock connection to IPG 809

 

 

 

 

OTHER PRODUCTS IN THE SAME CATEGORY:
Loading...