The surge current generators generate standard impulse currents with waveform 8/20 µs according to IEC, EN, VDE. Pulse current output amplitude is controlled by preset charging voltage and can be adjusted up to the maximum value of the special type of generator. The generators are designed for testing electrical components, overvoltage protectors and electronic circuits. They possess an electronically regulated high-voltage power supply, which allows an excellent reproducibility of the pulse output amplitude.
pulse current test of surge protection devices
The surge current generators PG **-*** generate standard impulse currents with waveform 8/20 µs according to IEC, EN, VDE. Pulse current output amplitude is controlled by preset charging voltage and can be adjusted up to the maximum value of the special type of generator. The generators are designed for testing electrical components, over-voltage protectors and electronic circuits. They possess an electronically regulated high-voltage power supply, which allows an excellent reproducibility of the pulse output amplitude.
The pulse-forming network contains a pulse-fidelity current viewing resistor for monitoring the output waveform. The impulse current output is located at the top of the equipment and provides high-current connectors for a plug-in test adapter.
All generators feature a microprocessor controlled user interface and display unit for ease of use. The microprocessor allows the user to either execute
standard test routines, or a ´user-defined´ test sequence. The test parameters, which are shown on the built-in display, are easily adjusted by means of the rotary encoder. A standard parallel interface provides the ability to print a summary of the test parameters whilst testing is being carried out.
Technical specification: |
|
Mainframe: | |
Microprocessor controlled LCD display | 8*40 characters |
Remote control via an optically isolated computer interface | 5 m fiber optic cable |
Parallel printer interface for on-line documentation | 25-way ´D´ connector |
External Trigger input | 10 V at 1 kW |
External Trigger output | 10 V at 1 kW |
Connector for external safety interlock loop | 24 V = |
and external red and green warning lamps acc. to VDE 0104 | 230 V, 60W |
Mains power | 230 V, 50/60 Hz |
OPTION 1: | Remote control PC Software Incl. 5 m long fiber optic cable and USB-PC Interface. |
OPTION 2: | Test chamber on top, build in 19” rack, with security glass door, safety interlock protects the high-voltage output terminals. Upon opening of the door, switching-off of the generator or mains blackout a built-in high-voltage grounding switch discharges the test object and the internal energy storage capacitor. Test space ca. W*H*D 470*530*490 mm³ |
OPTION 3: | Current impulse triggering synchronization 0-360° to the zero crossings of the sinusoidal mains voltage, phase angle in steps of 1°. Mains power (E.U.T. power supply) 400Veff / 50Hz Without decoupling from HV – power supply. |
OPTION 4: | Galvanic isolated measurement of current impulse with a Pierson coil. |
OPTION 5: | Polycarbonate security door with solid hinges and fasteners made of stainless steel. |
Technical Specifications: | PG 12-3600 |
Surge Current Generator | |
Peak value of charging voltage, adjustable | 0 - 12 000 V, ± 2% |
Max. stored energy | 3600 Ws |
Charging time for max. charging voltage | < 60 sec |
Waveform of impulse output current acc. to IEC 60-2 | 8 / 20 µs ± 20 % |
Impulse output current, adjustable via charging voltage | 2 - 40 kA ± 5 % |
Output pulse polarity, switchable | POS/NEG/ALT |
HV output: high current terminals on the top of the equipment | |
Current viewing resistor, built-in | 0.5 mW, 10 MHz |
Max. pulse repetition rate | 1/60 sec |
Dimensions: 19"-cabinet W * H * D | ca. 553*1600*600 mm3 |
Weight | 95 kg |
Surge Current Generator | PG 12-5000 |
Peak value of charging voltage, adjustable, | 0 - 12 500 V, ± 2% |
Max. stored energy | 5000 Ws |
Charging time for max. charging voltage | < 60 sec |
Waveform of impulse output current acc. to IEC 60-2 | 8 / 20 µs ± 20 % |
Impulse output current, adjustable via charging voltage | 2 - 50 kA ± 5 % |
Output pulse polarity, switchable | POS/NEG/ALT |
HV output: high current terminals on the top of the equipment | |
Current viewing resistor, built-in | 0.5 mW, 10 MHz |
Max. pulse repetition rate | 1/60 sec |
Dimensions: 19"-cabinet W * H * D | ca. 553*1600*600 mm3 |
Weight | 95 kg |
Surge Current Generator | PG 15-5600 |
Peak value of charging voltage, adjustable, | 0 - 15 kV, ± 2% |
Max. stored energy | 5600 Ws |
Charging time for max. charging voltage | < 90 sec |
Waveform of impulse output current | 8 / 20 µs ± 20 % |
Impulse output current, adjustable via charging voltage | 2 - 50 kA ± 5 % |
Output pulse polarity, switchable | POS/NEG/ALT |
Current viewing resistor, built-in | 0.5 mW, 10 MHz |
Max. pulse repetition rate | 1/100 sec |
Dimensions: 19"-cabinet W * H * D | ca. 553*1600*600 mm3 |
Weight | 165 kg |
Surge Current Generator | PG 15-6600 |
Peak value of charging voltage, adjustable, | 0 - 15 kV, ± 2% |
Max. stored energy | 6600 Ws |
Charging time for max. charging voltage | < 90 sec |
Waveform of impulse output current acc. to IEC 60-2 | 8 / 20 µs ± 20 % |
Impulse output current, adjustable via charging voltage | 2 - 70 kA ± 5 % |
Output pulse polarity, switchable | POS/NEG/ALT |
HV output: high current terminals on the top of the equipment | |
Current viewing resistor, built-in | 0.5 mW, 10 MHz |
Max. pulse repetition rate | 1/120 sec |
Dimensions: 19"-cabinet W * H * D | ca. 553*1200*600 mm3 |
Weight | 165 kg |
Surge Current Generator | PG 20-14000 |
Peak value of charging voltage, adjustable, | 0 - 20 kV, ± 2% |
Max. stored energy | 14000 Ws |
Charging time for max. charging voltage | < 120 sec |
Waveform of impulse output current | 8 / 20 µs ± 20 % |
Impulse output current, adjustable via charging voltage | 2 - 100 kA ± 10 % |
Output pulse polarity, switchable | POS/NEG |
Current viewing resistor, built-in | 0.25 mW, 10 MHz |
Max. pulse repetition rate | 1/120 sec |
Dimensions: 19"-cabinet W * H * D | ca. 553*2000*600 mm3 |
Weight | 265 kg |
Surge Current Generator | PG 30-12500 |
Charging voltage adjustable | 0.2 - 30 kV ± 2 % |
Max. stored energy | 12500 Ws |
Charging time for max. charging voltage | < 120 sec |
Waveform of impulse output current acc. to IEC 60 - 2 | 8/20 µs ±20 % |
Impulse output current, adjustable via charging voltage | 1 - 60 kA ±10 % |
Output pulse polarity, fixed | NEG |
Surge current output terminal | high current plug |
Current viewing resistor, built-in | 0.25 mW, 10 MHz |
Max. pulse repetition rate | 1/120 sec |
Dimensions: : rack | ca. 1000*1100*600 mm3 |