HVTS 30-20 & HVTS 30-40, 30 kV, High Voltage AC Test Set

The High-Voltage Test-Set HVTS 30-20/ 30-40 is designed for high-voltage testing of the electrical insulation of electrical equipment and electrical systems. Test voltage adjustable up to 30 kV, 1-20 mA/ 1-40mA. The High-Voltage Test-Set HVTS mainly consists of a high-voltage transformer and a control and display unit. The primary voltage of the high-voltage transformer is generated by a motor-driven variac. The output voltage can be selected from 0.2 to 30 kV with a voltage rise adjustable from 0,4 kV/sec to 30 kV/sec.

PARTNER:

MARKETS:

TEST STANDARDS:

Data Sheet

SPECIFICATIONS

High-Voltage AC-Test-Set 

 

 

HVTS 30-20  /  HVTS 30-40

Max. test voltage 30 kV» 

 
  • Rise of sinus voltage ramp
  • 0.2 - 30 kV/sec
  • Output current 1 – 20 / 40 mA 
 

The High-Voltage Test-Set HVTS 30-20/ 30-40 is designed for high-voltage testing of the electrical insulation of electrical equipment and electrical systems. Test voltage adjustable up to 30 kV, 1-20 mA/ 1-40mA. The High-Voltage Test-Set HVTS mainly consists of a high- voltage transformer and a control and display unit. The primary voltage of the high-voltage transformer is generated by a motor-driven variac. The output voltage can be selected from 0.2 to 30 kV with a voltage rise adjustable from 0,4 kV/sec to 30 kV/sec.

 

Maximum output current is 20mA / 40mA. The output voltage is measured by a built-in capacitive voltage divider.

 

The HVTS 30-20/ 30-40 features a microprocessor-controlled user interface and a 5” touch screen unit for ease of use. The microprocessor allows the user to execute either standard test routines or a “user-defined” test sequence. A standard USB port provides the ability to print a summary of the test parameters to a USB stick.

 
Technical specification HVTS 30-20 HVTS 30-40
Mainframe control unit:  
Microprocessor controlled touch panel 5”, 800X480, 24 bit
Optical EthernetInterface for remote control of the generator optional
Interface for saving reports USB
Connector for external safety interlock loop 24 V =
external red and green warning lamps acc. to VDE 0104 230 V, 60W
   
HV unit:  
Test voltage, adjustable 0,2 - 30 kV»/
Accuracy of the test voltage < 2%
max. test current, overcurrent switch-off 1- 20mA 1- 40mA
Output current in mode “burn”, adjustable 1- 20mA 1- 40mA
Accuracy of the test current ( from upper range value ) +/- 2%
Rise of sinus voltage ramp, adjustable 0,24 - 30 kV/sec
Test time at selected voltage level, adjustable 1 - 100 s
High-voltage output, one terminal connected to GND hv bushing
Connection for ground rod M 6
Ground rod 0.7 m long
Mains power 230 V , 50/60 Hz, 1250 VA
   
Dimensions      W * H * D 553*800*1250 mm3
Weight 60 kg
Option:  
Test chamber on top, build in 19” rack, with security glass door, safety interlock protects the high-voltage output terminals.Upon opening of the door or switching-off of the generator, the HV output switch off.Test space ca.                                                     W*H*D     470*530*490 mm³

 

 

 